- Power Cables[4]
- Contact Person : Mr. TONG Daniel
- Company Name : Ningbo JJ Import & Export Co., Ltd.
- Tel : 0086-574-86321168
- Fax : 0086-574-86321105
- Address : Zhejiang,Ningbo,Number 118, Zhuangshi Avenue,Zhenghai district
- Country/Region : China
Related Product Searches:220KV Power cable W/T Optic Fiber,High Quality XLPE insulated Power Cable,XLPE insulated Power Cable 500kV Power cable W/T Optic Fiber
JJ Import & Export Co., LTD is the distributor for Orient Cable. We represent all the types of their products in Africa,South Asia, Middle East and South America.
Application:
1.Rated voltage U0/U:127/220kV, Max. voltage Um=252kV.
2.Max. long-term operating temperature of conductor 90°C.
3.Max. short-circuit temperature of conductor shall not exceed 250°C(5s Max.duration).
4.The ambient temperature under installation should not below 0°C, the min.bending radius ≥18D.(D means diameter).
Product Performance:
1.When the cable imposed 1.5U. voltage, it cannot be detected. discharge; when 2.5U. voltage imposed during 30min, cable cannot be breakdown.
2.Insulated cores not more than 5%(Tmax- Tmin/Tmax×100%≤5%).
3. 800mm² or above adopt segmentation structure.
4.No 30μm micro-hole on the insulation and no larger than 125μm opaque translucent dark and brown impurities no greater than 160μm.
5.Semi conducting layer jut is not more than 80μm, no 50μm micro-hole on the semi conducting layer and insulation interface.
Type and Description
Copper | Aluminum | Description | |||||||||
YJLW02 | YJLLW02 | XLPE insulated corrugated aluminum armored PVC Power Cable | |||||||||
YJLW03 | YJLLW03 | XLPE insulated corrugated aluminum armored PE Power Cable | |||||||||
YJLW02-Z | YJLLW02-Z | Longitudinal water blocking XLPE insulated corrugated AL armored PVC Power Cable | |||||||||
YJLW03-Z | YJLLW03-Z | Longitudinal water blocking XLPE insulated corrugated AL armored PE Power Cable |
YJLW02(03) YJLW02(03) -Z | ||||||||
Rated | Nominal section | Cable. Dia. (Nominal) | Cable Weight | Current Capacity A (Single grounding or cross-bonding) | ||||
voltage kV | mm² | mm | (Approximate)kg/km | direct buried in earth | in air | |||
YJLW02-Z | YJLW03-Z | Parallel laying | triple laying | Parallel laying | triple laying | |||
220 KV | 400 | 121 | 13920 | 13030 | 682 | 610 | 862 | 870 |
500 | 124 | 15520 | 14610 | 774 | 695 | 1002 | 1011 | |
630 | 127 | 17160 | 16230 | 875 | 782 | 1159 | 1172 | |
800 | 129 | 19320 | 18370 | 1003 | 910 | 1372 | 1395 | |
1000 | 132 | 21620 | 20650 | 1110 | 1016 | 1560 | 1589 | |
1200 | 136 | 23760 | 22760 | 1181 | 1181 | 1694 | 1742 | |
1400 | 140 | 26270 | 25240 | 1252 | 1252 | 1845 | 1907 | |
1600 | 143 | 28370 | 27310 | 1310 | 1310 | 1958 | 2038 | |
1800 | 147 | 30810 | 29720 | 1355 | 1355 | 2066 | 2158 | |
2000 | 149 | 33040 | 31940 | 1392 | 1392 | 2164 | 2271 | |
2500 | 157 | 38440 | 37270 | 1450 | 1450 | 2356 | 2514 |
Note: 1. Conductor working temperature 90°C, ambient temperature 20°C.
2. Installation buried depth 1m,Environmental thermal resistance coefficient 1.2K·m/W.
3. The distance between cable is 250mm when laying.